Site visit or send-in evaluation
Share the full encoder order code, controller, node ID and bit rate, current symptoms, bus layout and installation photos. Capture any existing presets and resolution settings before replacing the encoder. Use the enquiry form to share the details.
What specialist testing can show
A compatible CANopen master can check boot-up, heartbeat, error messages and position PDOs. A qualified technician can compare bus waveforms, supply voltage under load and repeatable position over multiple turns. Test a spare on an isolated service bus with the appropriate configuration before reconnecting it to production. Exact Mitchell TI-5000JX and TI-3000JX support was not verified for this CANopen encoder. POSITAL CANopen commissioning and diagnostics (PDF)
POSITAL IXARC UCD-CA01B-1312-HATS-2AW CANopen Encoder technical reference
Find your part number
Read UCD-CA01B-1312-HATS-2AW and product number 1618782. In this build, the 1312 field corresponds to 13 multiturn and 12 singleturn bits. Match the complete housing and termination fields before ordering or applying a wire map.
| Order code / item | Position and mounting | Connection |
|---|---|---|
| UCD-CA01B-1312-HATS-2AW · 1618782 | 13 MT + 12 ST, Ø10 mm blind bore, Ø58 mm body | Axial 2 m factory PVC flying lead |
| UCD-CA01B-1312-HBS0-PRR · 1645162 | 13 MT + 12 ST. Read the separate HBS0 shaft dimensions. | M23 12-pin connection, separate pin map |
| UCD-CA01B-0016-H8PS-PRV · 1770216 | Singleturn, 16-bit, Ø8 mm blind bore | M12 build, separate pin map |
1618782 exact catalogue · 1645162 exact catalogue · 1770216 exact catalogue
Production and end-of-life status
POSITAL marks exact product 1618782 Established on its Product Life Cycle line. Confirm orderability and delivery for the full part code. Reviewed 7 November 2026. POSITAL exact lifecycle record
Specifications
| Parameter | Value |
|---|---|
| Measurement | Magnetic absolute. Self-powered multiturn pulse counter, no backup battery or gear. |
| Position range | 12 bits per turn (4096 positions), 13 multiturn bits (8192 turns), binary |
| Bus | CANopen DS-406, 20 kbit/s–1 Mbit/s, galvanically isolated transceiver |
| Supply and current | 9–30 V DC. ≤70 mA at 10 V DC and ≤50 mA at 24 V DC. |
| Fit and speed | Ø58 mm body, Ø10 mm blind bore × 28 mm depth, ≤3000 rpm |
| Misalignment | Static axial ±0.3 mm and radial ±0.5 mm. Dynamic axial ±0.1 mm and radial ±0.2 mm. |
| Environment and lead | IP66/IP67, fixed lead −30 to +80 °C and flexing lead −5 to +80 °C. 2 m PVC, 46 mm minimum bend radius fixed or 61 mm flexing. |
Mounting and fit
Slide the encoder’s blind bore onto the measured shaft and use the specified clamping arrangement and housing restraint. Match the shaft insertion length and mounting geometry to the Drawings tab. The housing restraint keeps the encoder body fixed while allowing the intended movement within the static and dynamic misalignment limits. Check for a bottomed-out shaft or an overconstrained mounting before tightening. The drawing and machine installation instructions govern fasteners and torque. POSITAL exact drawing and accessories
Interface and measuring method
The encoder publishes a digital position on a shared CANopen bus. The controller can receive a process data object (PDO) by the configured trigger and use service data objects (SDOs) for approved parameters. The controller and encoder need a unique node ID, matching bit rate and compatible EDS/configuration. A node can be visible and still report wrong travel if the scaling, direction, PDO mapping or preset differs.
The self-powered turn counter tracks rotation without a backup battery. Check machine reference separately from raw encoder position, especially after replacing or presetting an encoder. POSITAL CANopen overview · UCD CANopen user manual (PDF)
Verified wiring
| Lead colour | Function |
|---|---|
| Red | Encoder power supply |
| Yellow | Supply ground / return |
| White | CAN High |
| Brown | CAN Low |
| Green | CAN GND, bus reference |
Supply ground and CAN GND are listed separately. The installed bus drawing determines bonding and any shield treatment. The wire colours above apply to the exact factory lead, not to a generic M12 pinout. Use the connection plan for the other connector codes. POSITAL 1618782 Connection Plan · Separate M23 variant connection plan
Cables inside the motor and at the machine
This external unit comes with a 2 m axial PVC lead, 0.14 mm² conductors. It has no in-motor PCB-to-bulkhead harness. Use the network drawing to terminate the lead to the correct CAN branch. The separate HATS-PAV connector versions use a different ordering code and cable accessory. Match any replacement to the label, installation sealing and wire map. POSITAL exact lead and accessories
Fault checks
Before disturbing the bus or shaft. Follow your site’s lockout procedure. Secure the load against movement, isolate all motor, drive and separate feedback supplies, allow the specified discharge time and verify absence of voltage. A qualified technician should perform internal and electrical checks. Unplug or reconnect only with the applicable circuits safely de-energized. Preserve the network configuration and coordinate any isolated bus checks with the machine owner.
- Inspect. Check the shaft clamp and restraint, lead entry, bend radius, junction terminals, shield and connector contamination. Check that the encoder actually follows the measured shaft.
- Isolated cable checks. With the harness isolated from the encoder and receiver at both ends, use resistance mode. First short the meter probes to establish lead resistance. Check each conductor end to end and flex the cable gently at the strain relief. Check between unrelated wires and from signal wires to shield or shell. Expect open only where the drawing calls for isolation. Compare any intentional sense links or shield bonds with the equipment drawing. Keep insulation testers away from connected electronics. Confirm the CAN High and CAN Low pair and bus-reference continuity on a disconnected branch.
- Network and supply. Confirm the documented terminations at the ends of the bus. A qualified technician using an approved breakout fitted while off can measure the encoder supply from red to yellow. Check that the node uses the right bit rate, a unique ID and the intended NMT state.
- Interpret symptoms. All nodes dropping out suggests bus power, termination, a short or network configuration. One dead node suggests its branch, voltage or ID. Correct network traffic with wrong position suggests scaling, mapping or preset. Changes synchronized with shaft or cable movement call for checking the clamp and harness.
Motor and drive applications
Use this standalone encoder with a compatible CANopen master implementing the DS-406 encoder profile. The POSITAL manual distinguishes connector/cable UCD-CA01 units from connection-cap models with manual address and termination switches. Use the setup and EDS for the actual 2AW device, and confirm the controller’s bit rate and network topology. POSITAL CANopen UCD setup (PDF)
Angle of alignment and commissioning
For this machine-axis encoder, commissioning means mounting alignment, count direction, scaling and machine datum. Read the old node settings and reference before disconnecting. Apply a preset only when permitted by the machine procedure, at standstill, then verify it against a known reference. POSITAL documents preset object 6003h in its UCD manual. A motor commutation angle, if required by a separate servo, belongs to that motor system. POSITAL preset and configuration procedure (PDF)
Drawings, pin maps and manuals
- POSITAL 1618782 exact product page. Download the device data sheet and use the Connection Plan and Drawings tabs for the exact lead.
- POSITAL IXARC UCD CANopen manual (PDF). See sections on baud rate, node ID, PDO and preset.
- POSITAL CANopen technology reference. Network roles, messages and encoder integration.