Site visit or send-in evaluation
Share the resolver label, exact motor and drive codes, the alarm and when it occurs. Include photos of the mounting register and any motor bulkhead connector. A photo of the old wire terminations is particularly helpful after a rewire. Use the enquiry form to share the details.
What specialist testing can show
A Mitchell TI-5000JX can test this class of resolver using Generic Resolvers and its built-in resolver hardware. A qualified bench technician can set the approved excitation for the exact resolver, check angle and direction, and inspect sine and cosine envelopes with the TI-3011 breakout and an appropriate differential measurement setup.
A TI-3000JX Generic Resolver run test requires the motor pole count, 1X resolver setting, phase direction and a measured angle under the documented lockup reference. It requires a guarded fixture, suitable motor and verified commutation. Mitchell resolver checkout · Mitchell Generic Resolver run setup
LTN RE-21-1-A05 Resolver technical reference
Find your part number
Look for the complete RE-21-1-A05 marking. RE-21 identifies the frame family. The middle 1 corresponds to one pole pair in LTN’s A05 data. The A05 suffix selects the winding and electrical specification, which differs from other one-pole-pair RE-21 parts.
| Full LTN code | Pole pairs / ratio | Excitation winding | Each output winding |
|---|---|---|---|
| RE-21-1-A04 | 1 / 0.5 ±10% | 90 Ω ±10% | 72 Ω ±10% |
| RE-21-1-A05 | 1 / 0.5 ±10% | 48 Ω ±10% | 31 Ω ±10% |
| RE-21-1-A06 | 1 / 0.5 ±10% | 61 Ω ±10% | 53 Ω ±10% |
| RE-21-1-A07 | 1 / 1.0 ±10% | 90 Ω ±10% | 260 Ω ±10% |
A matching frame and pole count are only part of the replacement check. Compare the winding and the motor’s fit and excitation specification. LTN electrical selection table (PDF) · Matching SpareFaber spare

Production and end-of-life status
LTN still provides RE-21 product information that names A05. Manufacturer production and an exact approved successor remain unconfirmed. SpareFaber has a separate catalogue listing for the matching spare. Reviewed 7 November 2026. LTN current RE-21 document (PDF) · SpareFaber A05 stock listing
Specifications
| Parameter | Value |
|---|---|
| Measuring method | Passive 1X frameless resolver, one electrical angle cycle per shaft turn |
| Excitation reference | 7 V AC nominal (7 Vrms in the earlier LTN sheet). Current 70 mA ±10% at the 7 V, 4 kHz condition in the linked electrical table. |
| Transformation ratio and phase shift | 0.5 ±10%. Carrier phase shift 8° ±3° at the stated 7 V, 4 kHz condition. |
| Room-temperature winding resistance | Primary 48 Ω ±10%. Each secondary 31 Ω ±10%. |
| Resolver accuracy | ±5 arcminutes with 9 arcminutes spread in the LTN table. The drive adds its own conversion error. |
| Fit | Ø12.7 H8 rotor bore on the illustrated drawing. Size 21 family. Select the drawing that matches the recess and stator register. |
| Component limits and leads | ≤20,000 rpm, −55 to +155 °C, minimum 300 mm AWG 24 leads in the linked LTN table. |
The LTN table’s test conditions and the Parker drive’s excitation are separate. Use the approved motor and drive values in service, and compare RMS and peak-to-peak only after accounting for the waveform. LTN drawing and specifications (PDF) · Earlier LTN RMS notation (PDF)
Mounting and fit
The rotor slides onto the motor shaft. The stator sits concentrically in the end housing and stays fixed to the motor. Neither part supplies its own bearing. The motor controls rotor position, running clearance and retention. Photograph the rotor orientation and stator location before disassembly.
On the LTN drawing with the Ø50.77 mm register, the reference shaft is Ø12.7 g7 and the rotor bore is Ø12.7 H8. LTN publishes several outlines on the same sheet. Compare the recess, stator locating diameter, axial offset and retention details with the original motor. Avoid loading the windings, and route the leads away from rotating parts. Use the exact motor assembly procedure for fasteners, shims or adhesive. LTN resolver mating geometry (PDF)
Interface and measuring method
The drive feeds an AC carrier to R1/R2. The rotor position modulates the same carrier in two outputs. S1/S3 is the cosine winding and S2/S4 is sine. At a stationary angle the carrier is still present. The drive demodulates the two channels to calculate angle from their ratio and sign.
If the pairs are swapped or one pair’s polarity is reversed, the drive can show smooth motion with the wrong angle or direction. Check both output amplitudes over a full safe turn, since a single channel can naturally be near zero at a particular shaft angle.
Verified wiring
| Circuit | LTN leads | Parker X18 pins |
|---|---|---|
| Excitation R1 / R2 | Red/white / black/white | 4 REF+ / 15 REF− |
| Cosine S1 / S3 | Red / black | 12 COS+ / 11 COS− |
| Sine S2 / S4 | Yellow / blue | 8 SIN+ / 7 SIN− |
Match the actual motor harness and connector orientation before termination. The X18 numbers are for the Parker resolver-configured high-density Sub-D input in section 4.6.2. The resolver has no dedicated supply or temperature lead on this six-lead map. The X18 temperature circuit is separate. LTN lead and polarity drawing (PDF) · Parker PSD1-S X18 drawing (PDF)
Cables inside the motor and at the machine
LTN shows six open AWG 24 PTFE leads, 300 mm on the standard outline. There is no universal motor-end plug on this resolver. Ask the motor manufacturer for the motor-side loom using the exact motor model, connector and serial number. A replacement harness needs three correct pairs, the original polarity, temperature routing where present, and the drive maker’s shield termination. The Parker X18 table applies to the drive end only. LTN open-end leads (PDF) · Parker motor feedback connection instructions (PDF)
Fault checks
Isolate first. Follow your site’s lockout procedure. Secure the load against movement, isolate all motor, drive and separate feedback supplies, allow the specified discharge time and verify absence of voltage. A qualified technician should perform internal and electrical checks. Unplug or reconnect only with the applicable circuits safely de-energized.
- Look and document. Check plug latch, pushed-back pins, oil, foreign material, damaged shielding and strain relief. Look for a shifted stator, rub marks and altered axial spacing after a bearing repair.
- Check the harness separately. With the harness isolated from the encoder and receiver at both ends, use resistance mode. First short the meter probes to establish lead resistance. Check each conductor end to end and flex the cable gently at the strain relief. Check between unrelated wires and from signal wires to shield or shell. Expect open only where the drawing calls for isolation. Compare any intentional sense links or shield bonds with the equipment drawing. Keep insulation testers away from connected electronics.
- Measure each winding directly. With the resolver disconnected, use resistance mode across the named pair. At room temperature, 48 Ω ±10% is about 43.2–52.8 Ω on R1/R2, and 31 Ω ±10% is about 27.9–34.1 Ω on each output. A reading taken through the drive or a cable can obscure the source. Compare both secondary readings and check for unintended links between winding pairs.
- Check excitation and output on an approved setup. A qualified person can fit a breakout while isolated and use an appropriate differential scope or resolver tester. Compare the carrier across R1/R2 and the two return envelopes at the same angle. An ordinary meter can miss or misread a kilohertz carrier. If the drive has excitation but the resolver does not, trace the harness. If the signals are sound at the drive and the shaft reads backward or trips on torque enable, verify polarity, motor phase order and alignment.
Motor and drive applications
Parker specifically lists RE-21-1-A05 for its PSD1 resolver feedback option. In the PSD1-S section 4.6.2 the X18 drawing gives the drive’s 8 kHz carrier and maximum 9.5 V peak-to-peak excitation. This is a verified receiver application. Confirm the motor code and receiver configuration when selecting replacement parts. Parker PSD1-S resolver compatibility and wiring (PDF)
Angle of alignment and commissioning
This passive resolver supplies angle-dependent windings and has no electronic memory to clone. Preserve the old mechanical index and read the drive’s existing offset where documented. Use the motor or drive commissioning procedure to set the new commutation offset and confirm direction. Mitchell’s Generic Resolver run setup uses the angle measured at a +U/−V lockup reference. That is a bench reference for the approved motor and setup. An exact offset in electrical degrees requires the specific motor, pole count and phase convention. Mitchell angle convention and guarded run setup
Drawings, pin maps and manuals
- LTN RE-21 mechanical drawings and electrical data (PDF). Page 1 for dimensions and wiring, page 2 for the A05 winding table.
- LTN frameless resolver catalogue (PDF). See RE-21 for the A04, A05, A06 and A07 variants.
- Parker PSD1 installation guide 192-011006N10 (PDF). Sections 4.6.2 and 5.8.2 cover the resolver-configured drive connector.
- Mitchell Generic Resolvers. Check setup and excitation limits against the exact resolver.