Site visit or bench evaluation
Request a site visit if the fault follows cable movement, starts when the drive enables or returns when the motor warms up. Share the full motor and encoder codes, drive model, fault history and connector photos. For send-in evaluation, keep the original encoder and motor together when alignment is in question. SICK specifies replacement of a defective EKM36-2 assembly. Rockwell assigns internal Kinetix VPL service to its qualified personnel. SICK operating instructions (PDF) · Rockwell VPL installation instructions (PDF)
What specialist testing can show
Mitchell’s TI-5000JX with the TI-5106 HIPERFACE DSL adapter, matched test lead and Athena profile can check count and direction, read encoder errors, display electrical angle and read memory on supported OEM motors. Mitchell lists TI-5734 for most VPL motors, TI-5738 for certain larger M40 VP builds and TI-5743 for direct-to-encoder DSL testing. Check the motor connector and profile first. These are bench leads. Mitchell TI-5106 coverage · Mitchell VPL setup and test leads
Mitchell demonstrates a TI-3000JX run test on a supported VPL motor. A run test requires the correct motor and amplifier setup, a secured fixture, matched cables, and verified feedback and commutation before rotation. Mitchell VPL run-test reference
SICK EKM36 technical reference
Read the full EKM36 label
The reference model here is EKM36-2KF0B018A, SICK item 1084235. M means multiturn, 2 identifies the safety variant, K is the motor-cable integration option and 18 specifies the bits per revolution. For the hardware revision, look at A or B after KF0. The final A is a separate character. Write down the exact motor code and serial number as well.
| Model and SICK item | Position data | Variant and DSL connector |
|---|---|---|
| EKM36-2KF0B018A 1084235 |
18 bits per turn, 4,096 turns | Safety variant. Hardware B has a housing connection on pin 4. |
| EKM36-2KF0A018A 1054316 |
18 bits per turn, 4,096 turns | Earlier safety variant. Hardware A uses pins 2 and 3 for DSL. |
| EKM36-0KF0B018A 1084233 |
18 bits per turn, 4,096 turns | Standard variant. Hardware B adds the housing connection on pin 4. |
| EKM36-0KF0A018A 1053849 |
18 bits per turn, 4,096 turns | Earlier standard variant. Hardware A uses pins 2 and 3 for DSL. |
| EKM36-2KF0B020A 1084236 |
20 bits per turn, 4,096 turns | Safety variant. Hardware B with a higher position resolution. |
| EKS36-2KF0B018A 1084231 |
18 bits, single-turn | Safety variant. Hardware B with position within one revolution. |
Match resolution, safety variant and motor configuration as well as fit. If your label reads 1053849, see the SpareFaber listing for that exact spare. SICK type code and ordering table (PDF)
Production and end-of-life status
SICK identifies hardware B as the successor to hardware A. For the 18-bit multiturn models above, 1054316 corresponds to 1084235 and 1053849 to 1084233. Check the motor maker’s approved replacement and shielding arrangement before a swap. SICK still publishes a data sheet for 1084235. Current production or stock for that exact B item and OEM-coded units requires manufacturer confirmation. Checked 7 November 2026. SICK hardware A-to-B notice
Specifications for EKM36-2KF0B018A
| Parameter | Value for this part |
|---|---|
| Measuring method | Optical absolute multiturn, digital HIPERFACE DSL |
| Resolution and range | 18 bits (262,144 positions per revolution), 4,096 distinguishable turns |
| System accuracy | ±120 arcseconds |
| Supply and current | 7–12 V DC, 8 V recommended. ≤150 mA operating current with the specified interface circuit. See the startup current diagram separately. |
| User memory | 8,192 bytes. The motor maker determines what data is stored. |
| Shaft and housing | 1:3 tapered shaft, spring stator coupling, Ø35 mm body. IP40 with connectors inserted and cover closed. |
| Permissible shaft movement | Static ±0.1 mm radial / ±0.5 mm axial. Dynamic ±0.05 mm radial / ±0.1 mm axial. |
| Encoder operating speed | ≤9,000 rpm in the B-version data sheet. Observe the motor’s own limits. |
| Operating temperature | −20 to +115 °C with the stated thermal connection. Internal sensor temperature ≤125 °C. |
| Safety variant | SIL 2 / PL d capability in a suitable drive and installation, subject to SICK’s integration and commissioning conditions. |
The archived 1054316 sheet gives a different speed specification for hardware A, including a separate limit at switch-on or reset. Check the approved limit for the fitted part and motor before replacing it. SICK 1084235 data sheet (PDF) · SICK 1054316 archived data sheet (PDF)
How the tapered shaft fits the motor
The encoder’s tapered shaft seats in the motor shaft. Its M4 thread holds that joint together. Two M3 screws secure the spring stator plate to the motor flange on the documented Ø38 mm bolt circle. The plate holds the body against rotation while accommodating the designed shaft movement. Compare the taper, axial seating and fixing holes with SICK’s attachment drawing. Where OEM service access permits, check that the joint is seated, the plate fasteners are secure and the lead is free of pinching.
For EKM36-2 tapered mounting, SICK’s assembly instructions specify tool BEF-MW-EKX36 (2060224), final shaft tightening of 4 N·m with a +0.8 N·m tolerance, and 0.8 ±0.08 N·m for each M3 plate screw. Before the taper seats, the manual limits the thread torque to 0.8 N·m. Follow the specified sequence and keep the taper clean and dry. Use these figures for the illustrated SICK assembly and check the motor service procedure. SICK EKM36-2 §4 and Fig. 4 (PDF) · SICK outline and attachment drawings (PDF)
How HIPERFACE DSL exchanges information
Two conductors carry encoder power and digital communication. The drive’s DSL master supplies DC and exchanges messages on the same DSL+ and DSL− pair. In a one-cable motor, that feedback pair runs alongside separate motor power and brake conductors.
The drive receives absolute shaft position, status and supported diagnostic data. It uses the position to calculate speed and commutate the motor. A steady DC voltage across the pair establishes that the supply is present. A DSL master is needed to determine whether the data is healthy. Legacy HIPERFACE, as used by the SKM36, uses a separate analog sine/cosine path and a different interface. SICK HIPERFACE DSL master manual (PDF)
Verified DSL pins at the encoder, motor and drive
Use the numbered view in SICK’s connector drawing and check the key and molded pin numbers on the actual plug. With the latch feature above the pins as drawn, SICK numbers the communication connector 1–4 left to right. Verify pin numbers before working from the opposite side. The table lists the encoder connector, with SICK lead colours where specified.
| Pin | Hardware A | Hardware B | SICK lead |
|---|---|---|---|
| 1 | Unused | Unused | Leave free |
| 2 | +US / DSL+ | +US / DSL+ | Grey |
| 3 | 0 V / DSL− | 0 V / DSL− | Green |
| 4 | Unused | Housing / shield contact | Shield or drain on the specified B lead |
SICK lists JST GHR-04V-S as the mating housing for the 1084235 DSL connector. Its separate temperature-sensor socket uses pin 1 T+ and pin 2 T−, with Harwin M80-8990205 as the recommended mate. Follow SICK’s insulation requirements for that thermistor circuit. SICK 1084235 connector drawings (PDF)
For the Rockwell VPL-B1306C-PJ14AA M23 SpeedTec motor connector, E is DATA+ and H is DATA−. The VPL-B1654D M40 diagram instead uses L for DATA+ and H for DATA−. At the Kinetix 5500 drive’s MF connector, MF-1 is D+ (blue) and MF-2 is D− (white/blue) on the specified Rockwell lead. Use the applicable OEM diagram at each end. These hybrid motor plugs also contain motor power and brake contacts. Rockwell VPL motor plug drawings (PDF) · Kinetix 5500 MF connector, Table 45 (PDF)
Internal leads, housings and hybrid motor cables
| SICK type | Order no. | Length and termination |
|---|---|---|
| DOL-0B02-G0M2XC1 | 2062083 | 200 mm, two-wire twisted unshielded |
| DOL-0B02-G0M3XC1 | 2091818 | 300 mm, two-wire twisted unshielded |
| DOL-0B02-G0M4XC1 | 2086286 | 400 mm, two-wire twisted unshielded |
| DOL-0B03-G0M4XC1 | 2087314 | 430 mm, shielded DSL pair with drain to pin 4 for hardware B |
SICK suggests shielded leads above 200 mm inside the motor. Match the OEM’s approved routing, shield termination and lead length. The SICK leads listed here terminate in flying leads at the motor end. Obtain the complete PCB-to-bulkhead loom or mating connector from the motor maker by exact motor code. SICK in-motor cable options
Rockwell lists 2090-CSxM1DF external hybrid cables for Kinetix 5500 and 2090-CSxM1DG with longer feedback leads for the Kinetix 5700 layout. The 2198-KITCON-DSL is the Kinetix 5500 drive-end connector kit. Select the complete cable number by motor, drive, brake and length. Rockwell cable and shield-clamp guidance (PDF)
Fault checks on the machine
Read the drive before opening the cable. On a Kinetix 5500 with the equipment in its approved diagnostic state, open Diagnostics → Encoder Diagnostics. Record SUPP VOLT, LINK QUAL, RSSI and the fault log. Rockwell specifies 100% link quality and 80–100% RSSI on this display. Persistent drops warrant a check of the feedback shield bond and cable.
| Observation | Next check |
|---|---|
| Supply low or encoder data unavailable | Check the drive’s feedback supply and the two-wire path. If communication is down, the encoder voltage readout may be unavailable. Use the approved breakout procedure below. |
| Voltage in range, link drops or FLT S45 on Kinetix 5500 | S45 indicates feedback data loss. Check both plugs, cable flex points, shield bonding and the approved hybrid cable before replacing the encoder. |
| Link established, FLT S47 or encoder status fault | S47 is a feedback device failure report. Save the full code and details. Check the encoder status and verify on an approved known-good feedback path. |
| Link healthy, rough start or wrong position after service | Verify the motor data, shaft attachment, feedback direction and motor-specific commutation offset. If the motor position tracks but the load slips, inspect the coupling and load path. |
Isolated checks. Lock out power, secure the axis and suspended or stored-energy loads, and verify discharge per the drive manual. With the cable disconnected at both ends, check for backed-out or bent pins, dirt, moisture and latch damage. Meter each DSL conductor end to end, then check for shorts between the pair and to the housing or shield. Flex only the disconnected cable during the check. Compare shield continuity with the OEM drawing and keep an insulation tester away from the encoder and drive electronics.
Powered supply check for qualified personnel. Fit an approved breakout with power isolated. With the axis secured in the OEM-approved diagnostic state, put the meter in DC volts with the leads in V and COM. At the 1084235 encoder end, measure red on 2 (DSL+) and black on 3 (DSL−) under load. Expect 7–12 V DC. Compare with the approved drive-side reading if low. Keep the shield on its specified path. Use a DSL diagnostic tool to check communication.
Kinetix 5500 Encoder Diagnostics (PDF) · SICK DSL communication monitoring note (PDF)
Documented motor and drive applications
Mitchell documents EKM36 on the tested Allen-Bradley VPL-B1306C-PJ14AA. Rockwell confirms that its P option is 18-bit multiturn HIPERFACE DSL. Rockwell documents EKM36-2 for the W safety feedback option on specified VPL frames. Confirm the encoder label and the motor’s approved spare for the actual assembly. Mitchell VPL example · Rockwell VPL functional-safety options (PDF)
Kollmorgen’s AKM connectivity table identifies GF as the EKM36 multiturn DSL option and GE as the EKS36 single-turn option. Use the complete AKM code and the drive-specific hybrid cable or feedback interface for that build. Kollmorgen AKM connector and feedback options
Commutation angle and encoder memory
Mitchell documents a motor-specific commutation reference stored with the motor data on Allen-Bradley VP DSL applications. Read and save the original report and memory using the matched VP DSL profile while the encoder is readable. Record the incoming electrical angle, phase convention and feedback direction. Use that motor’s reference for alignment. If the original data is unreadable, obtain the approved recovery procedure for that motor and serial number.
For an approved replacement, restore only the verified OEM data for that same motor using the approved procedure. Read it back and verify commutation and position independently before a guarded test. On safety applications, follow the OEM inspection and recommissioning procedure, including SICK’s specified feedback type verification. Mitchell VP DSL alignment memory support · SICK EKM36-2 commissioning (PDF)
Drawings, manuals and test references
- SICK 1084235 exact data sheet (PDF) with dimensions, plug drawings and accessories.
- SICK EKS36-2 / EKM36-2 operating instructions, 8020309/1JUA (PDF).
- SICK EKS36-0 / EKM36-0 operating instructions, 8020285/1R6J (PDF).
- Rockwell Kinetix VPL installation, VPL-IN001F (PDF) for motor codes and hybrid plugs.
- Rockwell Kinetix 5500 user manual, 2198-UM001N (PDF) for drive wiring, diagnostic screens and faults.
- Mitchell Allen-Bradley VPL test setup for adapter, leads, motor memory and run-test examples.